## Technical Overview: AKW401-R
The **AKW401-R** is a high-precision digital power meter (KW monitor) developed by Panasonic. It is designed to be DIN-rail mounted and is primarily used for monitoring power consumption in industrial machinery and electrical panels.
---
### 1. Key Electronic Components & Specifications
The AKW401-R consists of several internal modules including a micro-controller, high-speed sampling ADCs, and communication interfaces.
| Feature | Specification |
| :--- | :--- |
| **Input Voltage Range** | 100 to 240 V AC / 440 V AC (Depends on wiring) |
| **Phase Support** | Single-phase 2-wire, Single-phase 3-wire, 3-phase 3-wire |
| **Output Type** | Relay Output (Contact) + RS485 Communication |
| **Display Type** | 4-digit, 2-row LCD (Green/Red backlight) |
| **Current Measurement** | External CT (Current Transformer) required (5A / 50A / 100A / 250A / 400A / 600A) |
| **Accuracy** | Class 1.0 (IEC62053-21) |
---
### 2. Functional Electronic Blocks
1. **Sensing Circuit:**
* **Voltage Sensing:** High-impedance voltage dividers reduce the line voltage to levels manageable by the internal ADC.
* **Current Sensing:** Utilizes dedicated external **Current Transformers (CTs)**. The secondary current is converted into a proportional voltage signal across an internal burden resistor.
2. **Processing Unit:**
* A dedicated **ASIC/Microcontroller** performs True RMS calculations. It integrates instantaneous power (V x I) over time to calculate Active Energy (kWh).
3. **Output & Interface:**
* **RS485 Port:** Uses Modbus RTU or MEWTOCOL protocol for data logging to a PLC or PC.
* **Pulse/Alarm Output:** An open-collector or relay output that triggers based on specific power thresholds or integrates energy consumption pulses.
4. **Power Supply:**
* An internal switching mode power supply (SMPS) converts the AC input to DC for the logic circuits.
---
### 3. Connection Terminals
| Terminal ID | Description |
| :--- | :--- |
| **L1, L2, L3** | Voltage measurement inputs (Phase lines) |
| **N** | Neutral line (for single-phase 3-wire) |
| **CT1+, CT1- / CT2+, CT2-** | Secondary side connections for Current Transformers |
| **RS485 (+, -)** | Serial communication wires |
| **Out (R)** | Relay output for alarms or control signals |
---
### 4. Application Logic
The device calculates several electrical parameters simultaneously:
* **Active Power (kW)**
* **Integrated Energy (kWh)**
* **Current (A) and Voltage (V)**
* **Power Factor (PF)**
* **Frequency (Hz)**
---
- ⤷What is the compatible Current Transformer (CT) secondary current for this model?
- ⤷ How do I configure the Modbus RTU address on the AKW401-R?
- ⤷ Can this device measure reactive power (kVAR)?