FLM-DE-R
AI

The **FLM-DE-R** is a specialized electronic component, typically identified as a **Bus-Powered Field Link Module** (Digital Input/Output) within industrial fire alarm and security systems (specifically the Bosch LSN network). It serves as an interface between a fire panel and external devices.
---
### 1. Technical Specifications
Below are the primary electronic characteristics and ratings for the module:
| Parameter | Specification |
| :--- | :--- |
| **Input Voltage** | 15 V DC to 33 V DC (via LSN bus) |
| **Current Consumption** | Max 0.6 mA |
| **Relay Contact Rating** | 1 A at 30 V DC |
| **Protection Class** | IP 30 (standard enclosure) |
| **Operating Temperature** | -20 °C to +50 °C |
| **Addressing** | Via rotary switches or software |
---
### 2. Core Electronic Components & Functions
The module architecture consists of three main functional blocks:
#### A. The LSN Bus Interface
The "Heart" of the module is the **LSN (Local Security Network) Controller IC**.
- **Communication:** It uses a proprietary protocol to talk to the fire panel.
- **Power Management:** It extracts power directly from the data loop, meaning it does not require an external power supply for basic operation.
- **Isolation:** It features integrated isolators that ensure the rest of the loop continues to function if a short circuit occurs at this specific node.
#### B. Relay Outputs (The "R" in DE-R)
The "R" designation signifies a **Relay** output.
- **Electronic Switch:** It uses a dry-contact relay that allows the fire panel to trigger external hardware (such as door closers, fans, or sirens).
- **Feedback:** The module monitors the state of the relay to ensure it has successfully switched.
#### C. Input Monitoring Circuitry
The module includes digital inputs designed to monitor "normally open" or "normally closed" contacts.
- **End-of-Line (EOL) Resistors:** The electronic circuit uses resistors to monitor the line for three states: *Idle, Triggered,* and *Fault (Wire Break/Short).*
- **Debounce Logic:** Internal filtering prevents false alarms caused by electrical noise or "contact bounce."
---
### 3. Connection Terminals
The electronic wiring is generally distributed across the following terminal blocks:
1. **LSN In/Out:** Connects to the main data loop from the fire panel.
2. **Input Terminals:** For monitoring external sensors (e.g., flow switches).
3. **Relay Terminals:** COM (Common), NO (Normally Open), and NC (Normally Closed) contacts.
---
### 4. Rotary Switch Addressing
On the PCB (Printed Circuit Board), you will find **Rotary Switches**. These allow the technician to manually set the electronic address (001–254) for the module so the fire panel can identify its specific location in the building.
- ⤷
What is the maximum distance allowed for the LSN bus cable connected to this module?
- ⤷ How do you configure the EOL resistor values for the input monitoring?
- ⤷ Can the FLM-DE-R handle AC voltages on its relay contacts?