M2AMS-A1B-R2/UL
AI

The **M2AMS-A1B-R2/UL** is a specific model of an **Alternating Relay** (also known as a duplex controller) manufactured by **Macromatic Industrial Controls**. These devices are primarily used to balance the runtime of two electrical loads, such as pumps or compressors.
---
### ## Technical Specifications & Components
The model number identifies several key electronic and physical characteristics:
| Feature | Specification |
| :--- | :--- |
| **Input Voltage** | 120V AC (50/60Hz) |
| **Output Contacts** | DPDT (Double Pole, Double Throw) |
| **Mounting** | 8-Pin Round (Octal) Plug-in |
| **Max Power Consumption** | Approx. 3 VA |
| **Contact Rating** | 10A @ 240V AC / 30V DC (Resistive) |
| **Operating Temperature** | -28°C to 65°C (-18°F to 149°F) |
| **Certification** | UL Listed (Underwriters Laboratories) |
---
### ### Internal Electronic Functions
The "Electronic Parts" of this relay consist of a solid-state control circuit that manages the mechanical switching of the internal relays.
1. **Solid-State Logic Circuitry:**
Unlike a purely mechanical relay, this unit uses a CMOS logic circuit to "remember" which load was energized last. Even if power is lost, the device retains the memory of the sequence so it can alternate correctly upon the next cycle.
2. **Electromagnetic Coils:**
The unit contains two internal coils that actuate the DPDT contacts. When the external control switch (like a float switch) closes, the logic circuit directs power to the appropriate coil.
3. **Cross-Wired DPDT Contacts:**
The "A1B" designation indicates a specific contact arrangement. In the **"A" (Alternating)** mode, the relay switches between Load 1 and Load 2 every time the control switch is cycled. The **DPDT** configuration allows for complex wiring, such as controlling two separate motor starters or providing status signals.
4. **LED Indicator:**
Most R2/UL models include a top-mounted LED to indicate the current status of the relay or the position of the internal switch.
---
### ### Operation Logic (Sequence)
The electronic parts follow this repeating cycle:
1. **Initial State:** Control switch opens; Load 1 and 2 are OFF.
2. **Cycle 1:** Control switch closes; Logic activates Relay A -> Load 1 runs.
3. **Cycle 2:** Control switch opens; Load 1 stops; Logic flips the internal sequence.
4. **Cycle 3:** Control switch closes; Logic activates Relay B -> Load 2 runs.
---
### ### Wiring Diagram Overview (8-Pin)
The physical pins on the bottom of the unit are assigned as follows:
* **Pins 2 & 7:** Input Voltage (120V AC).
* **Pin 1:** Common for Contact 1.
* **Pin 8:** Common for Contact 2.
* **Pins 3, 4, 5, 6:** Normally Open (NO) and Normally Closed (NC) terminals for the two poles.
- ⤷
What is the difference between the 'A' and 'B' versions of Macromatic alternating relays?
- ⤷ Can this relay be used to run both pumps simultaneously in a lead-lag configuration?