M2AMS-A4-R/CE
AI

The **M2AMS-A4-R/CE** is a high-performance, rail-mounted signal conditioner (transducer) manufactured by **M-System**. It is specifically designed to accept a DC input signal and provide two independent, isolated DC output signals.
Below is a breakdown of its technical specifications and electronic characteristics.
### 1. Key Technical Specifications
| Feature | Specification |
| :--- | :--- |
| **Model Type** | Ultra-Slim Signal Conditioner (M2 Series) |
| **Input Signal** | 4 – 20 mA DC |
| **Output 1** | 4 – 20 mA DC |
| **Output 2** | 4 – 20 mA DC |
| **Power Input** | 100 – 240V AC (indicated by /CE marking) |
| **Isolation** | 4-way isolation (input to output 1 to output 2 to power) |
| **Mounting** | DIN Rail (35mm) |
---
### 2. Electronic Component Characteristics
#### A. Circuitry & Isolation
The device utilizes a **4-way isolation** architecture. This prevents ground loops and protects sensitive PLC/DCS equipment from high-voltage surges or electrical noise originating from the field sensors.
* **Isolation Resistance:** $\ge$ 100 M$\Omega$ with 500V DC.
* **Dielectric Strength:** 2000V AC @1 minute (input to output to power to ground).
#### B. Performance Accuracy
* **Accuracy:** $\pm$ 0.1% of span.
* **Temperature Coefficient:** $\pm$ 0.015% per °C (or $\pm$ 0.008% per °F).
* **Response Time:** $\le$ 0.5 seconds (0 – 90%).
#### C. Power Requirements
The **"R"** in the model code typically indicates the power supply type, and the **/CE** suffix confirms compliance with European Safety and EMC standards.
* **Power Consumption:** Approx. 3 VA at 100V AC; 4 VA at 240V AC.
* **Operating Temperature:** -5 to +55°C (23 to 131°F).
---
### 3. Pin Configuration & Wiring
The unit features screw terminals for secure connections. The standard wiring logic is as follows:
| Terminal No. | Function |
| :--- | :--- |
| **1 & 2** | Output 1 (+) / (-) |
| **3 & 4** | Output 2 (+) / (-) |
| **5 & 6** | Input (+) / (-) |
| **7 & 8** | Power Supply (L / N) |
---
### 4. Meaning of the Model Suffix (/CE)
The **/CE** marking is crucial for industrial applications as it guarantees:
1. **Electromagnetic Compatibility (EMC):** The device does not emit excessive interference and is resistant to external electrical noise.
2. **Low Voltage Directive (LVD):** Ensures the insulation and structural integrity are safe for high-voltage power inputs.
- ⤷
What is the difference between the M2AMS and the M2V series?
- ⤷ Can this model be used with a 24V DC power supply instead of AC?