M2SES-1AA-R2/CE
AI

The **M2SES-1AA-R2/CE** is a high-precision, plug-in type Signal Conditioner (Isolator) manufactured by **M-System**. It is part of the Mini-M series, designed to provide electrical isolation and signal conversion between industrial instruments.
### 1. General Specifications
This device acts as a buffer to prevent ground loops and protect sensitive control systems (like PLCs or DCS) from electrical noise and surges on the field side.
| Feature | Specification |
| :--- | :--- |
| **Model Series** | Mini-M Series (M2SES) |
| **Input Signal** | 4 – 20 mA DC |
| **Output 1** | 4 – 20 mA DC |
| **Output 2** | 4 – 20 mA DC |
| **Power Supply** | 100 – 240 V AC (Standard) |
| **Mounting** | Plug-in Socket (surface or DIN rail) |
| **Standards** | CE Marking (EMC Directive) |
---
### 2. Key Electronic Components & Internal Functions
The internal architecture of the M2SES-1AA-R2/CE relies on three primary stages to ensure signal integrity:
#### A. Input Stage
* **Precision Resistor:** Converts the 4-20mA current loop into a voltage signal.
* **Filtering Circuit:** Uses capacitors and inductors to suppress High-Frequency (HF) noise often found in industrial environments.
#### B. Isolation Stage (The Core)
* **Optical or Transformer Isolation:** This part physically separates the input, output, and power circuits.
* **Purpose:** It ensures that a high-voltage surge on the input side does not travel through to the output (protecting the PLC).
#### C. Output Stage
* **Operational Amplifiers (Op-Amps):** These provide high-impedance buffering and gain adjustment to ensure the output remains a steady 4-20mA regardless of the load resistance (up to 550Ω).
* **Zero/Span Adjustments:** Potentiometers located on the front panel allow for fine-tuning the electronic calibration of the output signals.
---
### 3. Terminal Assignment (Typical)
The device uses a base socket for wiring. Below is the standard pin configuration for the R2/CE model:
| Pin No. | Function | Description |
| :--- | :--- | :--- |
| 1 | Output 1 (+) | Positive 4-20mA signal |
| 2 | Output 1 (-) | Negative 4-20mA signal |
| 3 | Output 2 (+) | Positive 4-20mA signal |
| 4 | Output 2 (-) | Negative 4-20mA signal |
| 5 | Input (+) | Positive Current Input |
| 6 | Input (-) | Negative Current Input |
| 7 | Power (L) | AC Line Power |
| 8 | Power (N) | AC Neutral Power |
---
### 4. Technical Performance
* **Accuracy:** ±0.1% of span.
* **Response Time:** ≤ 0.5 seconds (0 – 90%).
* **Isolation Resistance:** 100 MΩ minimum with 500V DC.
* **Dielectric Strength:** 2000V AC @ 1 minute (Input to Output to Power to Ground).
---
- ⤷
What is the maximum load resistance allowed for the 4-20mA output signals?
- ⤷ How does 'Dual Output' functionality benefit a control system architecture?
- ⤷ Does this model require a specific base socket for DIN rail mounting?