M2UDS2-CB-R2
AI

The **M2UDS2-CB-R2** is a specific model within the **M2 Series** of signal conditioners manufactured by **M-System**. This particular unit is a **Potentiometer Transmitter**, designed to detect the position (resistance) of a potentiometer and convert it into a standard DC output signal.
---
### 1. Model Breakdown
The alphanumeric code describes the specific hardware configuration:
| Code Segment | Description |
| :--- | :--- |
| **M2UDS2** | Base model: Potentiometer Transmitter (Plug-in type) |
| **-C** | Power Input: 24V DC |
| **-B** | Output 1: 2 to 10V DC |
| **-R2** | Output 2: 4 to 20mA DC |
---
### 2. Key Technical Specifications
Below are the electronic characteristics essential for integration:
| Feature | Specification |
| :--- | :--- |
| **Input Type** | Potentiometer (3-wire) |
| **Input Resistance** | Total resistance 100 $\Omega$ to 10 k$\Omega$ |
| **Reference Voltage** | Approx. 0.5V DC |
| **Output 1 (Voltage)** | 2 – 10V DC (Load resistance $\geq$ 10 k$\Omega$) |
| **Output 2 (Current)** | 4 – 20mA DC (Load resistance $\leq$ 350 $\Omega$) |
| **Power Supply** | 24V DC ($\pm$10%, ripple 10% p-p max) |
| **Isolation** | 3-way (Input to Output to Power) |
| **Response Time** | $\leq$ 0.5 seconds (0 – 90%) |
---
### 3. Electronic Architecture
The M2UDS2 functions through several internal electronic stages:
1. **Input Conditioning:** The device applies a small reference voltage across the potentiometer. The wiper position creates a ratio-metric voltage.
2. **Isolation Barrier:** Uses optical or magnetic coupling to isolate the input circuit from the output and power circuits. This prevents ground loops and protects the PLC/DCS from surges.
3. **Signal Conversion:** An internal amplifier scales the millivolt-level signal from the potentiometer to the desired linear DC range.
4. **Dual Output Driver:** The "R2" designation indicates independent drivers for the voltage and current outputs, allowing you to send the signal to two different devices (e.g., a local display and a remote PLC).
---
### 4. Connection Diagram (Standard)
The unit typically uses a 10-pin or 11-pin plug-in base.
```text
[Input Terminals]
Pin 1: High (CW)
Pin 2: Wiper
Pin 3: Low (CCW)
[Output Terminals]
Pin 4(+)/5(-): Output 1 (2-10V)
Pin 6(+)/7(-): Output 2 (4-20mA)
[Power]
Pin 10(+)/11(-): 24V DC
```
---
- ⤷