M2VF-4WA-R2/CE
AI

The **M2VF-4WA-R2/CE** is a high-performance electronic signal conditioner (specifically a transducer or transmitter) manufactured by **M-System**. It is designed to convert an AC voltage input into a standardized DC output signal.
Below is a breakdown of its technical specifications and electronic characteristics.
---
### 1. Product Identification
| Component | Description |
| :--- | :--- |
| **Model Series** | M2VF (Plug-in Signal Conditioner) |
| **Input Type** | AC Voltage (Sine wave) |
| **Output Type** | DC Voltage or Current (Dual/Single output options) |
| **Housing** | Plug-in base for easy maintenance |
### 2. Electronic Specifications
This device uses analog-to-DC conversion circuitry to provide isolation and signal scaling.
| Parameter | Specification |
| :--- | :--- |
| **Power Input (R2)** | 100 – 240V AC (Operating range 85 – 264V AC) |
| **Input Range (4W)** | 0 – 110V AC (Standard utility/transformer voltage) |
| **Output Range (A)** | 4 – 20 mA DC (Load resistance max. 750 $\Omega$) |
| **Accuracy** | ±0.3% of span |
| **Response Time** | $\leq$ 0.5 seconds (0 – 90%) |
| **Insulation Resistance** | 100 M$\Omega$ at 500V DC |
| **Isolation** | Input to output to power to ground (2000V AC @ 1 min) |
---
### 3. Key Electronic Features
* **True RMS Conversion:** While standard models use mean value processing, specific variations of this series handle distorted waveforms by converting the RMS value of the AC input to a linear DC signal.
* **Isolation Circuitry:** It features high-voltage isolation between the input (high-voltage AC) and the output (low-voltage DC). This protects PLCs or SCADA systems from surges or ground loops.
* **Zero and Span Adjustment:** The front panel typically includes multi-turn potentiometers to calibrate the 0% and 100% signal points.
* **CE Marking:** The "/CE" suffix indicates the unit complies with European safety and Electromagnetic Compatibility (EMC) standards.
---
### 4. Connection Diagram (General Layout)
```text
[ AC INPUT ] ----> [ Rectifier/Filter ] ----> [ Isolation Transformer ] ----> [ DC OUTPUT ]
(Term 1,8) (Signal Cond.) (Opto/Magnetic) (Term 4,5)
```
### 5. Application Use-Case
The M2VF-4WA-R2/CE is primarily used in industrial power monitoring to:
1. Monitor line voltage from a Potential Transformer (PT).
2. Provide a feedback signal to a control system (PLC) regarding the health of a power grid.
3. Protect sensitive electronics by providing a 2000V AC isolation barrier.
---
- ⤷What is the difference between Mean Value and RMS conversion in this model?
- ⤷ How do I wire the M2VF-4WA-R2/CE for a 4-20mA loop?
- ⤷ Can this unit be mounted on a DIN rail?