M2VS-151-R2/CE
AI

The **M2VS-151-R2/CE** is a high-performance **Mini-M series signal conditioner** (isolator) manufactured by **M-System**. Its primary function is to accept a DC voltage input and provide an isolated DC output, typically used to prevent ground loops and protect control systems in industrial environments.
---
## 1. Technical Specifications
| Parameter | Specification |
| :--- | :--- |
| **Model Type** | Ultra-slim Signal Conditioner (Mini-M Series) |
| **Input Signal** | 1 – 5V DC |
| **Output Signal** | 4 – 20mA DC |
| **Power Input (R2)** | 100 – 240V AC |
| **Isolation** | 3-way (Input to Output to Power) |
| **Accuracy** | ±0.1% of span |
| **Response Time** | ≤ 0.5 seconds (0 – 90%) |
| **Mounting** | DIN Rail Mounting |
| **Standards** | CE Marking compliant |
---
## 2. Key Electronic Components & Design
### A. Input Section
The input stage uses a high-impedance circuit to ensure minimal loading on the source sensor. For the **"151"** configuration:
* **Input Impedance:** Typically 1 MΩ minimum.
* **Filtering:** Built-in low-pass filters to reject high-frequency noise and 50/60Hz interference.
### B. Isolation Barrier
The "CE" version features robust galvanic isolation. This is usually achieved via:
* **Optical Couplers or Transformers:** These components physically separate the input, output, and power circuits, preventing surge damage and eliminating common-mode noise.
* **Dielectric Strength:** Usually rated for 2000V AC for 1 minute.
### C. Power Supply (R2)
The **R2** designation indicates a universal AC power module:
* **Switching Regulator:** An internal high-efficiency AC/DC converter that handles a wide range of input voltages (100–240V AC) while maintaining stable internal DC rails.
---
## 3. Terminal Connection Map
| Terminal No. | Function | Description |
| :--- | :--- | :--- |
| **1** | Output (+) | 4 – 20mA Positive |
| **2** | Output (-) | 4 – 20mA Negative |
| **3** | Input (+) | 1 – 5V DC Positive |
| **4** | Input (-) | 1 – 5V DC Negative |
| **5** | Power (L) | 100 – 240V AC Line |
| **6** | Power (N) | 100 – 240V AC Neutral |
---
## 4. Application Use Case
This device is commonly found in PLC (Programmable Logic Controller) cabinets. If a field sensor sends a 1-5V signal that is susceptible to electrical noise or "ground loops" (voltage differences between the sensor ground and the PLC ground), the **M2VS-151** cleans the signal, converts it to a more robust 4-20mA current loop, and protects the PLC's sensitive input cards from high-voltage spikes.
- ⤷
How do I calibrate the zero and span on the M2VS-151?
- ⤷ What is the difference between the M2VS and the M2RS series?
- ⤷ Can this unit be powered by 24V DC instead of AC?