99 / 105 page ![]() 98 9.1 Purpose Japanese and international standards require, in sum- mary, that an overcurrent protector must be capable of interrupting the short-circuit current that may flow at the location of the protector. Thus it is necessary to establish practical methods for calculating short-cir- cuit currents for various circuit configurations in low- voltage systems. 9.2 Definitions 1. % Impedance The voltage drop resulting from the reference current, as a percentage of the reference voltage (used for short-circuit current calculations by the % impedance method). reference voltage voltage drop at capacity load % impedance = x 100 (%) (Reference voltage: 3-phase – phase voltage) 2. Reference Capacity The capacity determined from the rated current and voltage used for computing the % impedance (nor- mally 1000kVA is used). 3. Per-Unit Impedance The % impedance expressed as a decimal (used for short-circuit current calculations by the per-unit method). 4. Power Supply Short-Circuit Capacity 3-phase supply (MVA) = kl 3 x rated voltage (kV) x short circuit current (kA) 5. Power Supply Impedance Impedance computed from the short-circuit capacity of the supply (normally indicated by the electric power company; if not known, it is defined, together with the X/R ratio, as 1000MVA and X/R=25 for a 3-phase supply (from NEMA.AB1). 6. Motor contribution Current While a motor is rotating it acts as generator; in the event of a short circuit it contributes to increase the total short-circuit current. (Motor current contribution must be included when measuring 3-phase circuit short-circuit current). 7. Motor Impedance The internal impedance of a contributing motor. (A contributing motor equal to the capacity of the trans- former is assumed to be in the same position as the transformer, and its % impedance and X/R value are assumed as 25% and 6 (from NEMA.AB1). 8. Power Supply Overall Impedance The impedance vector sum of the supply (ZL), the transformer (ZT) and the motor (ZM). Overall impedance of 3-phase supply ZL + ZT + ZM (ZL + ZT) • ZM (Zs) = (% Ω) 9. Short-Circuit Current Measurement Locations In determining the interruption capacity required of the MCCB, generally, the short-circuit current is cal- culated from the impedance on the supply side of the breaker. Fig. 9.1 represents a summary of Japanese standards. 9.3 Impedances and Equivalent Circuits of Circuit Components In computing low-voltage short-circuit current, all im- pedances from the generator (motor) to the short-cir- cuit point must be included; also, the current contrib- uted by the motor operating as a load. The method is outlined below. 9.3.1 Impedances 1. Power Supply Impedance (ZL) The impedance from the power supply to the trans- former-primary terminals can be calculated from the short-circuit capacity specified by the power company, if known. Otherwise it should be defined, together with X/R, as 1000MVA and X/R=25 for a 3-phase supply. Note that it can be ignored completely if significantly smaller than the remaining circuit impedance. 2. Transformer Impedance (ZT) Together with the line impedance, this is the largest factor in determining the short-circuit current magni- tude. Transformer impedance is designated as a per- centage for the transformer capacity; thus it must be converted into a reference-capacity value (or if using Ohm’s law, into an ohmic value). Tables 9.1 show typical impedance values for trans- formers, which can be used when the transformer impedance is not known. 3. Motor Contribution Current and Impedance (ZM) The additional current contributed by one or more motors must be included, in considering the total 3- phase short-circuit current. Motor impedance depends on the type and capacity, etc.; however, for typical induction motors, % impedance can be taken as 25% and X/R as 6. The short-circuit current will thus in- crease according to the motor capacity, and the im- pedance up to the short-circuit point. The following assumptions can normally be made. a. The total current contribution can be considered as a single motor, positioned at the transformer location. b. The total input (VA) of motor contribution can be considered as equal to the capacity of the trans- former (even though in practice it is usually larger). Also, both the power factor and efficiency can be assumed to be 0.9; thus the resultant motor contri- bution output is approximately 80% of the trans- former capacity. c. The % impedance of the single motor can be con- sidered as 25% and the X/R as 6. 9. SHORT-CIRCUIT CURRENT CALCULATIONS |
|
Link URL |
| Does ALLDATASHEET help your business so far? [ DONATE ] |
About Alldatasheet | Advertisement | Contact us | Privacy Policy | Link to Datasheet | Link Exchange | Manufacturer List All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |