Features
Distributed DA&C Systems
ADAM-5000/485
ADAM-5000E
Introduction
The ADAM-5000/485 and ADAM-5000E systems use the EIA RS-485 communication protocol. This is the industry's most widely used, balanced, bidirectional transmission line
standard. The RS-485 was specifically developed for industrial applications to transmit and receive data at high rates over long distances.
Processor
CPU
16-bit microprocessor
I/O module capacity
4 or 8
Watchdog Timer
Yes
Power Consumption
1.0 W (ADAM-5000/485)
4.0 W (ADAM-5000E)
Isolation
Communication
2500 VDC (ADAM-5000/485)
Isolation
3000 VDC (ADAM-5000E)
Communication Power 3000 VDC
Isolation
I/O Module Isolation
3000 VDC
Diagnosis
Status Display
Power, CPU, communication
Self-test
Yes, while on
Software Diagnosis
Yes
Communication
Network
RS-232 or RS-485 (2-wire) to host
Speeds (bps)
1200, 2400, 4800, 9600, 19.2 k, 38.4 k, 57.6 k, and
115.2 kbps
Max. Communication
4000 feet (1.2 km)
Distance
Command Format
ASCII command/response protocol
Reliability Check
Communication error checking with checksum
Asynchronous
1 start bit, 8 data bits, 1 stop bit, no parity
Data Format
Maximum Nodes
Up to 256 multi-drop systems per host serial port
Protection
Transient suppression on
RS-485 communication lines
Power Requirements
Unregulated +10 to +30 VDC
Protected against Power Reversal
Power Protection
Transient suppression on power input
Mechanical
Case
KJW with captive mounting hardware
Plug-in Screw
Accepts 0.5 mm2 to 2.5 mm2 , 1 - #12 or 2 - #14 to
Terminal Block
#22 AWG
Environment
Operating Temperature -10 ~ 70° C (14 ~ 158° F)
Storage Temperature
-25 ~ 85° C (-13 ~ 185° F)
Humidity
5 ~ 95%, non-condensing
Ordering Information
ADAM-5000/485
Distributed DA&C System Based on RS-485 (4 slot)
ADAM-5000E
Distributed DA&C System Based on RS-485 (8 slot)
PCLS-OPC/ADM
OPC Server for ADAM-4000/5000 Series (RS-485)
PCLS-OCX
ActiveX Control for Data Acquisition and Control
PCLS-ADAMVIEW32
ADAMView Data Acquisition Software
RS-485 Communication for easy installation and networking
4 or 8 slots for up to 128 points data monitoning card control in one
module
Extensive Software support, inclucles windows DLL drivers, OCX drivers,
OPC server and popular HMI/SCAPA Software driver.
Seamlessly inteqrated with easy-to-use ADAMView data acquisition
Software.
Distributed DA&C System
Based on RS-485