6 / 9 page ![]() 6 Three-phase Input Switch Mode Power Supply S8VT Notice Three phase input operation when one phase is missing The S8VT will in most cases continue to operate even after the loss of one phase of the supply. The performance specifications are of course not guaranteed under these conditions. As the loss of one phase puts additional stress on some components, the life span of the unit could be shortened. It is prudent therefore to regularly check for signs of the following possible conditions. 1. Input terminals wiring open/loose. 2. Incorrect/No voltage on one or more phases of the supply. 3. Abrupt or periodical loss of input voltage. The power supply needs output derating as in the chart for the oper- ation on missing phase at the input voltage range of 340 to 576 V. Otherwise, the power supply may deteriorate or be damaged. In every single application suitability has to be checked. Note: In two phase operation, the specification for EMC perfor- mance, hold-up time, efficiency and output ripple will no longer be valid. Three phase input switch off In order to switch off the Power Supply completely: All 3 phases need to be switched off. Mounting To improve and maintain the reliability of the Power Supply over a long period, adequate consideration must be taken to heat radiation. The S8VT is designed to radiate heat by natural air cooling, there- fore, mount the S8VT so that enough air flow takes place around the power supply. If installing S8VTF closely, keep the minimum distance of 20 mm at 60°C ambient. Generating ( ±) Output Voltage An output of ±can be generated as shown below, since the S8VT has a floating output. Serial Operation As shown below, the output voltage from each S8VT can be added. Types must be the same. Parallel Operation As shown below, two S8VT-F (same capacity model) can be paral- leled to boost the output power (current). Set the output voltages of the Power Supplies to the same value. Also, make sure that the thickness and the length of all wires con- nected to the load are the same to ensure that the wires will have no voltage drop difference. Parallel connection is only permissible with ambient temperature from -10°C to +50°C. In case of a redundant system or back-up system, use diode to be connected to output + terminal of all the Power Supplies. -20 -10 0 10 20 30 Ta (°C) 40 50 60 70 80 0 10 20 30 40 50 60 Load (%) 70 80 90 100 110 Missing phase de-rating S8VT-F48024E S8VT-F96024E S8VT-F12024E S8VT-F24024E + V − V + V − V +V −V +V −V + V − V + V − V |
|
|
Link URL |
| Does ALLDATASHEET help your business so far? [ DONATE ] |
About Alldatasheet | Advertisement | Contact us | Privacy Policy | Link to Datasheet | Link Exchange | Manufacturer List All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |